Connecting Capacity
                    
                    
                        Busbar 10 / 10 mm², Flexible with Ferrule 0.75 ... 25 mm², Flexible 0.75 ... 25 mm², Rigid 0.75 ... 35 mm², Stranded 0.75 ... 35 mm²                    
                
                        Ambient Air Temperature
                    
                    
                        Operation -25 ... +55 °C, Storage -40 ... +70 °C                    
                
                        Screw Terminal Type
                    
                    
                        Failsafe Bi-directional Cylinder-lift Terminal                    
                
                        RoHS Status
                    
                    
                        Following EU Directive 2002/95/EC August 18, 2005 and amendment                    
                
                        Resistance to Vibrations acc. to IEC 60068-2-6
                    
                    
                        5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In                    
                
                        Resistance to Shock acc. to IEC 60068-2-27
                    
                    
                        25g / 2 shocks / 13 ms                    
                
                        Rated Ultimate Short-Circuit Breaking Capacity (Icu)
                    
                    
                        (230 V AC) 15 kA                    
                
                        Rated Service Short-Circuit Breaking Capacity (Ics)
                    
                    
                        (230 V AC) 11.2 kA                    
                
                        Rated Operational Voltage
                    
                    
                        acc. to IEC 60947-2 230 V AC                    
                
                        Rated Insulation Voltage (Ui)
                    
                    
                        acc. to IEC/EN 60664-1 440 V                    
                
                        Rated Impulse Withstand Voltage (Uimp)
                    
                    
                        4 kV, (6.2 kV @ sea level), (5.0 kV @ 2000 m)                    
                
                        Rated Frequency (F)
                    
                    
                        50 Hz, 60 Hz, DC Hz                    
                
                        Rated Current (In)
                    
                    
                        8 A                    
                
                        Power Loss
                    
                    
                        1.5 W at Rated Operating Conditions per Pole 1.5 W                    
                
                        Net Width
                    
                    
                        17.5 mm                    
                
                        Net Weight
                    
                    
                        0.125 kg                    
                
                        Net Height
                    
                    
                        111 mm                    
                
                        Net Depth / Length
                    
                    
                        69 mm                    
                
                        Mounting on DIN Rail
                    
                    
                        TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715, TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715                    
                
                        Minimum Order Quantity
                    
                    
                        1 piece                    
                
                        Mechanical Endurance (Nendu)
                    
                    
                        20000 cycle                    
                
                        Maximum Operating Voltage UL/CSA
                    
                    
                        277 V AC, 48 V DC                    
                
                        Interrupting Rating acc. to UL1077
                    
                    
                        (277 V AC) 10 kA                    
                
                        Housing Material
                    
                    
                        Insulation Group I, RAL 7035                    
                
                        Environmental Conditions
                    
                    
                        28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 %                    
                
                        Electrical Endurance
                    
                    
                        20000 AC cycle                    
                
                        Dielectric Test Voltage
                    
                    
                        50 / 60 Hz, 1 min: 2 kV                    
                
                        Degree of Protection
                    
                    
                        IP20                    
                
                        Contact Position Indication
                    
                    
                        Red ON / Green OFF                    
                
                        Connecting Capacity UL/CSA
                    
                    
                        Busbar 18-8 AWG, Conductor 18-4 AWG                    
                No Datasheet Available
 
                