ABB
ABB

AF110-30-11-70

Call for Price

Non-Reversing, 3-Pole Block Contactor, 100-250V 50/60Hz-DC Operated with Cable Clamp Terminals, 40 kW (1000V) Rated Power, 600 V Max. Operating Voltage, 10 million Mechanical Durability

Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Conventional Free-Air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A
Standard Auxiliary Contacts NO
1
Standard Auxiliary Contacts NC
1
Short-Circuit Protective Devices
gG Type Fuses 160 A
Rated Operational Voltage
Main Circuit 1000 V
Rated Operational Power AC-3 (Pe)
(220 / 230 / 240 V) 30 kW, (380 / 400 V) 55 kW, (415 V) 59 kW, (440 V) 59 kW, (500 V) 59 kW, (690 V) 75 kW, (1000 V) 40 kW
Rated Operational Current Ie, AC-1, AC-3 (A) - AC-3 55°C
110
Rated Operational Current Ie, AC-1, AC-3 (A) - AC-1 40°C
160
Rated Operational Current DC-5 (Ie)
(220 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-3 (Ie)
(220 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)
(220 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current AC-3 (Ie)
(1000 V) 55 °C 30 A, (690 V) 55 °C 82 A, (220 / 230 / 240 V) 55 °C 110 A, (415 V) 55 °C 110 A, (440 V) 55 °C 100 A, (380 / 400 V) 55 °C 110 A, (500 V) 55 °C 100 A
Rated Operational Current AC-1 (Ie)
(690 V) 55 °C 145 A, (690 V) 40 °C 160 A, (690 V) 70 °C 130 A
Rated Insulation Voltage (Ui)
acc. to UL/CSA 600 V, acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Rated Frequency (F)
Main Circuit 50/60 Hz
Rated Control Circuit Voltage (Uc)
60 Hz 100 ... 250 V, 50 Hz 100 ... 250 V, DC Operation 100 ... 250 V
Operate Time
Between Coil De-energization and NC Contact Closing 60 ... 130 ms
Net Width
102.0 mm
Net Weight
2.100 kg
Net Height
148.0 mm
Net Depth / Length
123.5 mm
Minimum Order Quantity
1 piece
Mechanical Durability
10 million
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
Horsepower Rating UL/CSA
(200-208 V AC) Three Phase 30 Hp, (440 ... 480 V AC) Three Phase 75 Hp. (550 ... 600 V AC) Three Phase 100 Hp, (220 ... 240 V AC) Three Phase 40 Hp
General Use Rating UL/CSA
(600 V AC) 140 A